JOSLYN, 1800-Series
Data and Signal Line Protector
1800-series
Series 1800 rail mounted protectors are designed to protect a wide array of twisted pair data and signal
interfaces. These Protectors have vibration proof screw terminals and flame resistant epoxy filled housing. The
cable shield passes through the protector and may either be grounded or floated by a two position ground link on
top of the protector.
Grounding
Proper grounding is essential for effective surge protector operation. The protector ground must be common with
equipment ground and provide a low resistance path to earth (facility) ground. The DIN clamp on the 1800 are
protector ground.
These protectors should be mounted directly to an earth grounded bus or transmitter. If the transmitter or bus is not solidly earth grounded, use a #6 AWG or larger copper wire to ground the bus or transmitter. The ground wire should be kept as short and straight as possible. Single point grounding will provide better protection, and will permit the protector to be located further from the equipment.
| Base Model | Appli- cation |
Interface Operating Characteristics |
Protective characteristics Peak Clamping Voltage |
Max . DC |
Typical Capacitance |
Series Resistance | ||||||
| Number (See Ordering Information for Suffix) |
Peak Signal Voltage |
Max. Data Rate |
@500 Amps, 8x20sec Surge and Voltage Rate-of Rise of 100 kV/sec |
@1000 Amps, 8x20sec Surge and Voltage Rate-of Rise of 500 kV/sec |
Current | Each Line (Input to Output) | ||||||
| - | - | L/L | L/G | - | L/L | L/G | L/L | L/G | - | L/L | L/G | - |
| (V) | (V) | (MHz) | (V) | (V) | (V) | (V) | (mA) | (pF) | (pF) | (Ohms) | ||
|
1810-10-AX 1811-10-AX 1820-10-AX 1821-10-AX 1810-15-AX 1811-15-AX 1820-15-AX 1821-15-AX 1810-28-AX 1811-28-AX 1820-28-AX 1821-28-AX 1810-50-AX 1820-50-AX |
- - RS-422 - RS-232 - RS-485 - - - 4-20 mA - - - |
20 20 10 10 30 30 15 15 56 56 28 28 100 50 |
10 10 10 10 15 15 15 15 28 28 28 28 50 50 |
10 50 4 50 8 45 3 45 9 40 4 40 10 4 |
50 60 25 30 70 80 35 40 110 120 55 60 178 89 |
25 30 25 30 35 40 35 40 55 60 55 60 89 89 |
42 52 21 26 56 64 28 32 90 100 45 50 156 78 |
21 26 21 26 28 32 28 32 45 50 45 50 78 78 |
220 350 220 350 180 300 180 300 150 250 150 250 100 100 |
1200 45 3300 65 750 45 2300 65 600 45 1800 65 500 800 |
2200 45 3300 65 1500 45 2300 65 1100 45 1800 65 300 800 |
10 10 10 10 15 15 15 15 22 22 22 22 51 51 |
| Add -A1 to base model number for DIN-1 clamp (example 1820-28-A1) |
Add -A3 to base model number for DIN-3 clamp (example 1820-28-A3) |